{"product_id":"edwards-fx-278","title":"EDWARDS FX-278","description":"\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eIntelligent addressable manual double-action pull station\u003c\/li\u003e\n\u003cli\u003eElectronic addressing without mechanical switches or DIP switches\u003c\/li\u003e\n\u003cli\u003eRotary reset mechanism\u003c\/li\u003e\n\u003cli\u003e120VAC operation with screw terminal connections\u003c\/li\u003e\n\u003cli\u003eCompatible with intelligent fire alarm control panels\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eOperating Voltage: 120VAC\u003c\/li\u003e\n\u003cli\u003eCurrent Draw: 350 microamps (standby), 500 microamps (activated)\u003c\/li\u003e\n\u003cli\u003eCommunication Line Voltage: Maximum 20V peak-to-peak\u003c\/li\u003e\n\u003cli\u003eAddressing: Configurable via control panel (01 to 127 addressable)\u003c\/li\u003e\n\u003cli\u003eMounting: North American 2.5\" deep 1-gang box or 4\" square box with 1.5\" deep 1-gang cover\u003c\/li\u003e\n\u003cli\u003eWire Size: 12, 14, 16, or 18 AWG (16 and 18 AWG preferred)\u003c\/li\u003e\n\u003cli\u003eOperating Temperature: 32 to 120°F (0 to 49°C)\u003c\/li\u003e\n\u003cli\u003eStorage Temperature: -4 to 140°F (-20 to 60°C)\u003c\/li\u003e\n\u003cli\u003eHumidity: 0 to 93% RH, noncondensing at 90°F\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCertifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eUL Listed for addressable systems\u003c\/li\u003e\n\u003cli\u003eNFPA 72 Compliant\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"EDWARDS","offers":[{"title":"Default Title","offer_id":54082205483315,"sku":"FX-278","price":72.75,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1000\/9785\/1699\/files\/FX-278.webp?v=1789514909","url":"https:\/\/plenasupply.com\/products\/edwards-fx-278","provider":"Plena Supply","version":"1.0","type":"link"}