Skip to product information
Need 20+ units? Request a quote →
EDWARDS FX-278 Pull Station
$69.39
Only 17 available
Ships In 1 Business Day Via FedEx
Manufacturer warranty
Edwards warranty
Covered by Edwards's standard manufacturer warranty. Contact us and we'll help you start an RMA with Edwards.
RMA help from Plena Supply
Need a return or replacement under warranty? Contact Plena Supply with your order number and the item's serial/date code, and we'll guide you through the RMA process.
Warranty terms are set by the manufacturer and can vary by product, date code and purchase channel.
30-Day Returns
Key Features
- Intelligent addressable manual double-action pull station
- Electronic addressing without mechanical switches or DIP switches
- Rotary reset mechanism
- 120VAC operation with screw terminal connections
- Compatible with intelligent fire alarm control panels
Technical Specifications
- Operating Voltage: 120VAC
- Current Draw: 350 microamps (standby), 500 microamps (activated)
- Communication Line Voltage: Maximum 20V peak-to-peak
- Addressing: Configurable via control panel (01 to 127 addressable)
- Mounting: North American 2.5" deep 1-gang box or 4" square box with 1.5" deep 1-gang cover
- Wire Size: 12, 14, 16, or 18 AWG (16 and 18 AWG preferred)
- Operating Temperature: 32 to 120°F (0 to 49°C)
- Storage Temperature: -4 to 140°F (-20 to 60°C)
- Humidity: 0 to 93% RH, noncondensing at 90°F
Certifications
- UL Listed for addressable systems
- NFPA 72 Compliant