HOCHIKI 0400-01079 SCI Short Circuit Isolator for 4" Box
Currently out of warehouse. Contact sales@plenasupply.com for lead time on incoming stock.
Manufacturer warranty
Hochiki warranty
Term 3 years from manufacture date (FireNET panels, modules, bases, detectors)
Hochiki America warrants FireNET panels, accessories, modules, bases and spot smoke/heat detectors for three years from the manufacture date. Other Hochiki parts carry 1 year from shipment or 18 months from manufacture; batteries are excluded.
RMA help from Plena Supply
Need a return or replacement under warranty? Contact Plena Supply with your order number and the item's serial/date code, and we'll guide you through the RMA process.
Warranty terms are set by the manufacturer and can vary by product, date code and purchase channel.
The Hochiki SCI (0400-01079) is a DCP short circuit isolator that mounts in a 4" square box. Placed anywhere on the SLC loop, it opens the loop during a downstream short so the rest of the loop keeps communicating, then restores the loop automatically when the short is removed.
Key Features
- Can be placed at any location on the SLC loop
- Checks the line for a short at power-up; relay stays open if a short is detected
- Yellow LED indicates an active short circuit
- Does not use an SLC address
- Supports Class A and Class B SLC wiring
- UL listed; CSFM and MEA listed
- Manufacturer: Hochiki | Part Number: 0400-01079 | Condition: New
Compatibility
UL listed compatible with Hochiki Digital Communications Protocol (DCP) control panel loops. Mounts in a 4" square electrical box or double-gang box.
Always verify compatibility with your system and local code requirements before ordering.
Technical Specifications
Manufacturer: Hochiki America
Model: SCI (part no. 0400-01079)
Type: SLC short circuit isolator module
Supply Voltage (S-SC): 25.3 ~ 39 VDC
Average Current: 270 µA typical; 10 mA in active short condition
Visual Indicator: Yellow LED: off normal, on active
Dimensions: 4.2" W x 4.7" H x 1.4" D
Weight: 1.4 oz
Operating Temperature: 32°F to 120°F (0°C to 49°C)
Relative Humidity: 90% RH non-condensing
Mounting: 4" square electrical box or double-gang box
Listings: CSFM 7300-0410:150; MEA 284-91-E Vol. IV